SCHRACK General Purpose Relays Power Relay RM C/D n 1 pole 30 A, 1 NO or 1 NO + 1 NC contact n Switching capacity up to 7500 VA n DC- or AC-coil n Push-to-test button n Chassis mount Applications Battery chargers, heating control F0166-B Approvals Z E214025 (for AgNi contacts in preparations) Technical data of approved types on request Contact data RMC RMD Contact configuration 1 NO and 1 NC 1 NO Contact set single bridging contact Type of interruption micro disconnection Rated voltage / max. switching voltage AC 400 / 440 VAC Rated current 30 A Maximum breaking capacity AC 7500 VA Limiting making capacity, max 20 ms 60 A Contact material AgCdO, AgNi Rated frequency of operation with / without load 16/100 min-1 Operate- / release time DC coil max 20/20 ms Bounce time DC coil NO / NC contact max 4/6 ms Contact ratings Type Contact Load UL 508 RMC/D NO / NC 30 A, 277 VAC, general purpose RMC/D NO / NC 30 A, 415 VAC, resistive Ambient temp. [C] Cycles 50C 50C 10x103 10x103 Coil data Rated coil voltage range DC coil AC coil Operative range to IEC 61810 6...220 VDC 6...400 VAC 2 Coil versions, DC-coil Coil code Rated Operate Release Coil Rated coil STD LED PD* LED+ voltage voltage voltage resistance power bipolar PD* VDC VDC VDC Ohm W 006 L06 0A6 LA6 6 4.5 0.6 32+10% 1.1 012 L12 0B2 LB2 12 9.0 1.2 110+10% 1.3 024 L24 0C4 LC4 24 18.0 2.4 475+10% 1.2 048 L48 0E8 LE8 48 36.0 4.8 2000+10% 1.2 060 L60 0G0 LG0 60 45.0 6.0 2850+10% 1.3 110 M10 1B0 MB0 110 82.5 11.0 10000+12% 1.2 221 N21 2C1 NC1 220 165.0 22.0 40000+15% 1.2 All figures are given for coil without preenergization, at ambient temperature +23C *) Protection diode PD; standard polarity: +A1 / -A2 1 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Power Relay RM C/D (Continued) Coil versions, AC-coil 50 / 60 Hz Coil code Rated STD LED voltage Terminal assignment Operate Release Coil Rated coil voltage voltage resistance power 50 / 60 Hz 50 / 60 Hz 50/ 60 Hz VAC VAC VAC Ohm VA 524 R24 24 19.2 / 20.4 9.6 80+10% 2.62 /2.00 548 R48 48 38.4 / 40.8 19.2 320+10% 2.60 / 2.17 560 R60 60 48.0 / 51.0 24.0 500+10% 2.62 / 2.20 615 S15 115 92.0 / 97.8 46.0 1850+10% 2.65 / 2.22 730 T30 230 184.0 / 195.5 92.0 7500+10% 2.69 / 2.26 900 V00 400 320.0 / 340.0 160.0 23500+15% 2.61 / 2.20 All figures are given for coil without preenergization, at ambient temperature +23C Bottom view on pins Insulation Dielectric strength coil-contact circuit open contact circuit Clearance / creepage coil-contact circuit Material group of insulation parts Insulation to IEC 61810-1 Type of insulation coil-contact circuit open contact circuit Rated insulation voltage Pollution degree Rated voltage system Overvoltage category 2500 Vrms 1500 Vrms W 4/14.9 mm IIIa S0269-AK 1 NO and 1 NC contact, RMC basic micro disconnection 250 V 3 230 / 400 V III Other data Mechanical endurance 10x106 cycles Material RoHS - Directive 2002/95/EC compliant as per product date code 0415 Environment Ambient temperature range DC coil -45...+60C AC coil -45...+40C Vibration resistance (function) NO / NC contact 10/5 g, 30...150 Hz Category of protection RTI - dust protected Processing Relay weight 81 g Packaging unit 10 pcs S0269-AH 1 NO contact, RMD S0269-AI 2 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change. SCHRACK General Purpose Relays Power Relay RM C/D (Continued) Dimensions Cover with mounting brackets, 6.3 mm quick connect terminals S0298-BK Product key Typical product key RM D 0 5 730 Type RM Power Relay RM C/D Contact configuration C 1 NO contact and 1 NC contact, 30 A D 1 NO contact, 30 A Version 0 AgCdO, without test button 3 AgCdO, with test button 2 AgNi, without test button 7 AgNi, with test button Enclosure 5 cover with mounting brackets, 6.3 mm quick connect terminals Coil Coil code: please refer to coil versions table, preferred types in bold print Product key RMC05024 RMC05524 RMC05615 RMC05730 RMC35024 RMD05024 RMD05524 RMD05615 RMD05730 RMD35024 RMD35730 Contacts 1 NO + 1 NC contact 30 A 1 NO contact 30 A Version without test button Enclosure mounting brackets quick c. 6.3 mm Coil DC-coil AC-coil with test button without test button DC-coil with test button DC-coil AC-coil AC-coil Coil 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 24 VDC 24 VAC 115 VAC 230 VAC 24 VDC 230 VAC Part number 4-1393844-5 1393146-5 8-1393147-7 1393146-6 1393146-7 1393146-9 1-1393146-1 1415009-1 4-1393844-7 2-1419136-2 1393097-5 3 Datasheet Rev. IJ1 Issued 2009/10 www.tycoelectronics.com www.schrackrelays.com Dimensions are in mm unless otherwise specified and are shown for reference purposes only. Product specification according to IEC 61810-1. Product data, technical parameters, test conditions and processing information only to be used together with the 'Definitions' section in the catalogue or at schrackrelays.com in the `Schrack' section. Specifications subject to change.